China Testing Instruments Manufacturer,Whatsapp/Wechat:+8618620373879  Email: 464560351@qq.com

MEWOI-High Voltage Insulation Tester GM3125
MEWOI-High Voltage Insulation Tester GM3125
MEWOI-High Voltage Insulation Tester GM3125
MEWOI-High Voltage Insulation Tester GM3125
MEWOI-High Voltage Insulation Tester GM3125
MEWOI-High Voltage Insulation Tester GM3125
MEWOI-High Voltage Insulation Tester GM3125
MEWOI-High Voltage Insulation Tester GM3125
MEWOI-High Voltage Insulation Tester GM3125
MEWOI-High Voltage Insulation Tester GM3125

MEWOI-High Voltage Insulation Tester GM3125

2023-08-10 11:44:04  

MEWOI-High Voltage Insulation Tester GM3125

  • Main Features :
  • Serial No. : Lisa0511
Contact US For Quotation  Email:464560351@qq.com  Whatsapp&Wechat:+8618620373879

MEWOI-High Voltage Insulation Tester GM3125

Features

High voltage insulation tester possesses the following features:

1.Auto- discharge function to make, the operation safe.
2.LCD Back-light.
3.Digital readout display.
4.Live circuit warning symbols with audio sounds.
5.Auto- power off function (in 10 minutes without operation)
6.Timer measurement function.
7.Low battery indication
8.PI measurement (Polarization index measurement)
9.Suitable for 12V DC adapter (12V/1A)

Specifications

1. Insulation resistance tester:

Rated voltage
500V1000V2500V5000V
Test range
0.0~99.9MΩ
100~999MΩ
0.0~99.9 MΩ
100~999 MΩ
1.00~1.99GΩ
0.0~99.9 MΩ
100~999 MΩ
1.00~1.99GΩ
10.0~99.9GΩ
0.0~99.9 MΩ
100~999 MΩ
1.00~9.99GΩ
10.0~99.9GΩ
100~1000GΩ
Open circuit voltage
DC 500V
+30%, -0%
DC 1000V
+20% -0%
DC 2500V
+20% -0%
DC 5000V
+20% -0%
Rated current
0.5MΩloading
1mA~1.2mA
1MΩ loading
1mA~1.2mA
2.5MΩ loading
1mA~1.2mA
5MΩ loading
1mA~1.2mA
Short- circuit current
Approx. 1.3mA
Accuracy
±5%rdg±3dgt (0~99.9GΩ)
±20%rdg±3dgt (above 100GΩ)

2. Voltage tester:

30~600V (Resolution 1V)


DV
AV
Measuring range
±30~±600V
30~600V(50/60Hz)
Resolution
1V
Accuracy
±2%rdg±3dgt

3.Technology parameter:

Technology parameter
Technology index
Display
Max. 999 counts LCD display(1000 counts only at 1T is displayed)
Over range indication
OL mark appears on insulation resistance range.
LO mark appears on voltage's range.
Auto- ranging
Range shifts to upper range: 1000 count
Range shifts to lower range: 95 counts
(merely on the insulation resistance range)
Sample rate
0.5~ 10 times/sec
Operable altitude
Less than 2000m (Indoor use)
Operation circumstance
Temperature 0~40℃, humidity <= 85%
Storage circumstance
Temperature -20~ 60 , humidity <= 90%
Overload protection
Insulation resistance : AC 1200V/ 10s
Voltage : AC 720V/ 10s
Voltage resistance
AC8320 (50/60Hz)/ 5 second (between electrical circuit and enclosure)
Insulation resistance
1000M of more/ DC 1000V (between electrical circuit and enclosure)
Power supply
DC12V (8x1.5V LR14 battery)
Battery's life
Approx. 15 hours
Dimension
153x 96 ×200mm
Weight
1032g (without batteries and test wires)