Contact US For Quotation | Email:464560351@qq.com | Whatsapp&Wechat:+8618620373879 |
MEWOI-ZC71 series programmable withstand voltage/insulation resistance tester
Description
Brief introduction
ZC71 series program-controlled AC and DC withstand voltage/insulation testers are the company's safety products. The instrument uses linear amplification technology to produce a low-distortion sine wave output, making the test more accurate. The use of a 16×2 large-character LCD display screen and a user-friendly interactive operation mode make it clearer and easier for users to understand. The test results and test conditions are displayed at the same time, which makes users feel at ease about the test conclusions. The instrument can be widely used in fields that require safety testing. |
Performance characteristics
16×2 large character LCD display Linear, low distortion sine wave output 5 groups of program setting and memory function Voltage ramp setting function Unique arc detection function, defect identification is more accurate ZC7110 has AC withstand voltage test function ZC7120 has AC and DC withstand voltage test function ZC7112 has AC withstand voltage/insulation test function ZC7122 has AC and DC withstand voltage/insulation test function |
Technical index
Model | ZC7122 | ZC7120 | ZC7112 | ZC7110 | |||
cross | The output voltage | Range: 0-5000V, 0-12mA, resolution 10V | |||||
Accuracy: ± (2% set value + 5V) | |||||||
Output frequency | 50Hz/60Hz selectable | ||||||
Output waveform | Sine wave, distortion degree <2% | ||||||
Upper limit setting | Range: 0.10-12.00mA, resolution 0.01mA | ||||||
Lower limit setting | Range: 0.00-12.00mA, resolution 0.01mA | ||||||
Arc detection | Level 1-9 | ||||||
straight | The output voltage | Range: 0-6000V, resolution: 10V, accuracy: ± (2% set value + 5V) | ----- | ----- | |||
Output ripple | <5% (6KV/5mA) tested under linear load | ----- | ----- | ||||
Upper limit setting | Range: 0.02-5.00mA, resolution: 0.01mA Accuracy: ±(2% set value + 2 words) | ----- | ----- | ||||
Lower limit setting | Range: 0.00-5.00mA, resolution 0.01mA Accuracy: ±(2% set value + 2 words) | ----- | ----- | ||||
Automatic discharge | 200mS | ----- | ----- | ||||
Control interface | Input: test(TEST), reset (RESET) | ||||||
Slow rise setting | 0.1-999.9 seconds | ||||||
testing time | Range: 0.5-999.9 seconds (0=continuous test) | ||||||
Test result output method | Buzzer, LCD display reading, control interface status output | ||||||
Memory group | 5 groups of test conditions are memorized, each group has 3 test steps to choose | ||||||
monitor | 16×2 LCD display with backlight | ||||||
Applicable to ZC7112/ZC7122 | |||||||
Absolutely | The output voltage | Range: DC100-1000V, resolution 10V | |||||
Resistance range | Range: DC100-1000V, resolution 10V | ||||||
Upper limit setting | Same resistance range, spacing 1MΩ | ||||||
Lower limit set point | Same resistance range, spacing 1MΩ |