China Testing Instruments Manufacturer,Whatsapp/Wechat:+8618620373879  Email: 464560351@qq.com

MEWOI-S020-20KV high voltage Electrician Prevent Electric Natural Rubber Insulated Insulating Gloves
MEWOI-S020-20KV high voltage Electrician Prevent Electric Natural Rubber Insulated Insulating Gloves
MEWOI-S020-20KV high voltage Electrician Prevent Electric Natural Rubber Insulated Insulating Gloves
MEWOI-S020-20KV high voltage Electrician Prevent Electric Natural Rubber Insulated Insulating Gloves
MEWOI-S020-20KV high voltage Electrician Prevent Electric Natural Rubber Insulated Insulating Gloves
MEWOI-S020-20KV high voltage Electrician Prevent Electric Natural Rubber Insulated Insulating Gloves
MEWOI-S020-20KV high voltage Electrician Prevent Electric Natural Rubber Insulated Insulating Gloves
MEWOI-S020-20KV high voltage Electrician Prevent Electric Natural Rubber Insulated Insulating Gloves

MEWOI-S020-20KV high voltage Electrician Prevent Electric Natural Rubber Insulated Insulating Gloves

2023-07-11 14:16:42  

20KV Insulating Gloves

  • Main Features :
  • Serial No. :
Contact Us For QuotationEmail:  464560351@qq.comWhatsapp&Wechat:+8618620373879

Introduction to insulating gloves for live working

With the excellent insulation property of rubber, the insulating gloves for live working are mainly made of imported high-quality rubber, mixed with additives with good insulation performance and reinforcement, and formed through a series of strict processes. After strict electrical performance test. High voltage withstand level, good physical and mechanical properties. Comfortable to wear. It is used to protect hands from electric shock when live working personnel contact live conductors and electrical equipment, so as to provide insulation protection for hands.

Insulating gloves for live working Applicable industry

Maintenance of electric power and electrical equipment, maintenance of power distribution room equipment, maintenance of electric locomotive and other live working places.

Type of insulating gloves for live working

At present, insulating gloves for live working are divided into latex impregnated gloves and injection molding gloves. Latex impregnated gloves are formed through a series of strict processing procedures by using the principle of ion adsorption, dipping ceramic molds into the latex solution for many times, controlling the thickness of gloves according to the voltage withstand level. The finished product is soft and seamless. Injection molding gloves are molded by an advanced injection molding machine at one time or by a mold. The overall density of the finished product is large, the bonding degree is high, and the sealing property is good.

Precautions for use and storage of insulating gloves for live working

1, The ex factory electrical insulation performance of this product is qualified. After purchasing gloves, if they are exposed to rain, moisture, mildew, or other abnormal changes during transportation and storage, they should go to the statutory testing agency for electrical performance review test.
2,Before use, it must be carefully checked. If any damage is found, it shall be immediately stopped and replaced.
3,During operation, the sleeve mouth shall be put into the barrel mouth to prevent accidents. After reuse, the internal and external dirt shall be wiped clean. After drying, it shall be sprinkled with talcum powder and placed flat to prevent damage under pressure. It shall not be placed in place.
4,It should be stored in a dry and ventilated warehouse with a room temperature of - 15 ℃ to+30 ℃ and a relative humidity of 50% to 80%, away from heat sources, more than 20 cm from the ground and walls, and protected from the impact of corrosive substances such as acid, alkali, oil, etc; Do not place it in the open air to avoid direct sunlight or on the ground.
5,Insulating gloves for live working shall be kept in the original package, with a shelf life of 24 months from the date of production; Preventive tests must be carried out every 6 months during storage or use.

Specification

Executive standard: 

Q/12XJ5206,GB/T 17622-2008,IEC 60903:2014 and EN60903
Length: 
410 ± 15mm
Structure: 
five fingered hand type, curling type
Level: 
Level 2
Test voltage: 
20kV
Material: 
rubber
Thickness: 
≤ 2.3mm
Color: 
orange
Application range: 
three-phase AC voltage below 10000V
Package: 
1 pair/box, 6 pairs/box, and 1 pair of sweat gloves for each pair
Weight: 
8.5kg
Volume: 
46cm × 41cm × 31cm


Technical parameters of insulating gloves for live working

levelVerification test voltage (AC) VMaximum allowed
leakage current
mA
Power test time
min
Maximum service voltage (V)
Ex factory
test
Ex factory
test
AC
Grade 00
(2.5kV)
2500123500
Level 0
(5kV)
5000163380
Level 1
(10kV)
100001833000
12kV120001838000
15kV150001939000
Level 2
(20kV)
2000020310000
25kV2500021321750
Level 3
(30kV)
3000024326500
35kV3500024330000
Level 4
(40kV)
4000024336000


Telephone
Email
Map
QQ Chat